PAC_STD_4T_208/230V/3PH/60HZ

50FC-A05A2A5-0A0A0
$0.00 / EACH
  • : Each
  • : Carrier
  • : Active
  • : Trading Goods (ZAW1)
  • : Technical Defect
  • Auto Enrichment Status: Done
  • Brand: Carrier
  • Efficiency: Standard
  • Manufacturer: Carrier
  • Nominal Capacity: 4 Ton
  • Nominal Capacity (Ton): 4 Ton
  • Product Line: WEATHERMAKER®
  • Refrigerant: R-410A
  • Airflow: 2000 (5 Ton)
  • Charge(A): 9-14
  • Coil Type: RTPF
  • Coil Type: RTPF
  • Fan Diameter: 16.6
  • Fan Diameter: 23°
  • Fla: 1.5
  • Oa Inlet Screen Quantity: Administrator
  • Certifications: AHRI
  • Condensate Drain Connection Size: 3/4
  • Fan Quantity: Administrator
  • Fpi: 18°
  • Lra: 83
  • Motor Drive Type: Direct
  • Oa Inlet Screen Size: 20x24x1
  • Compressor Type: Scroll
  • Cooling Capacity: 47
  • Fan Type: Vane Axial
  • Fpi: 15
  • Motor Hp: 1/4
  • Ra Filter Quantity: Editor
  • Rla: 13.7
  • Rows: Editor
  • Eer: 11.8
  • High Pressure Reset: 505
  • Max Cont Bhp: 1.06
  • Motor Quantity: Administrator
  • Ra Filter Size: 16x25x2
  • Rows: Reader
  • Total Face Area: 15.9
  • Fuse Amps: 30°
  • High Pressure Trip: 630
  • Motor Drive Type: Direct
  • Motor Rpm: 1100
  • Total Face Area: 5.5
  • Tube Diameter: 5/16
  • Low Pressure Reset: 117
  • Tube Diameter: 3/8
  • Tube Material/Fin Material: Cu/Al
  • Low Pressure Trip: 50-54
  • Motor Quantity: Administrator
  • Tube Material/Fin Material: Cu/Al
  • Metering Device: Acutrol
  • Minimum Circuit: 24°
  • Rpm Maximum: 2170
  • Number Of Circuit: Administrator
  • Rpm Minimum: EMERSON-SWAN
  • Seer: 1/4
  • Sound Level: BEACON/MORRIS
  • Number Of Compressor: Administrator
  • Total Power: Carrier
  • Refrigerant Type: R-410A

Electric Heat / Electric Cooling & Cooling Only with Ecoblue™ Technology

3 to 27.5 Nominal Tons

Exclusive, new EcoBlue™ Technology was designed to improve performance and efficiency while decreasing maintenance and installation costs. The industry’s first beltless direct-drive vane axial fan for rooftop units* is just one of many technological advances that prove that not all rooftop units are created equal. Other enhancements include a new control board and coil technology, permanently lubricated motor bearings, tool-less filter access doors and more – all available on this multiefficiency offering.

*Available on select models


Features

Performance Features

  • Meets and exceeds ASHRAE 90.1 energy efficiency levels
  • New unit control board with intuitive quick fan speed adjustment
  • New direct drive - EcoBlue™ Technology indoor fan system uses Vane Axial fan design & electronically commutated motor
  • Single-stage cooling capacity 04-06 models, two-stage on 07-30 models
  • SEERs up to 14.0, IEER of 15.2
  • Cooling operating range up to 115 °F (46°C) and down to 40°F (4°C) using winter start kit
  • Innovative corrosive-resistant composite condensate pan in accordance with ASHRAE 62 Standard, sloping design; side or center drain
  • Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
  • Units generally meet and exceed ASHRAE 90.1 energy efficiency levels. Review unit specific performance for compliance

Maintenance Features

  • New unit control board facilitating simple safety circuit troubleshooting and simplified control box arrangement as well as easy intuitive fan speed adjustment
  • Access panels with easy grip handles
  • Innovative, easy starting, no-strip screw feature on unit access panels
  • Tool-less filter access door
  • Optional hinged access panels also available
  • NEW Direct Drive – EcoBlue™ Technology Indoor fan system uses Vane Axial fan design and electronically commutated motor with beltless design
  • Two-inch disposable return air filters

Installation Features

  • Same footprint as prior Carrier models for that original fit; reduces installation costs and time
  • Field convertible from vertical to horizontal airflow configuration
  • Provisions for thru-the-bottom power entry capability as standard
  • Single point electric, and controls connections
  • Full perimeter base rail with built-in rigging adapters and fork truck slots

Reliability Features

  • Scroll compressors with internal line-break overload protection
  • 24-volt control circuit protected with resettable circuit breaker
  • Permanently lubricated direct-drive ECM evaporator-fan motor
  • Totally enclosed condenser motors with permanently lubricated bearings
  • Low pressure and high-pressure switch protection

Standard Limited Warranty

  • 5 years electric heaters
  • 5 years parts only compressor
  • 3 year SystemVu™ controller
  • One year parts only on all other parts
  • Additional extended warranty packages available
Options

Factory-Installed Options

  • Temperature Sensing EconoMi$er with relief
  • Enthalpy Sensing EconoMi$er with relief
  • Humidi-MiZer® Adaptive Dehumidification System
  • Return Air Smoke Detector
  • Supply Air Smoke Detector
  • CO2 Sensor
  • Condensate Overflow Protection
  • Multiple Static Fan Capabilities
  • Phase Monitor/Protection
  • Thru-The-Base Utility Connections
  • Louvered Hail Guards
  • Non-Fused Disconnect Switch
  • MERV-8 Return Air Filters
  • Hinged Access Panels
  • Unpowered Convenience Outlet
  • Powered Convenience Outlet
  • Coated Coils:
    • Pre-Coat
    • E-Coat
    • Copper/Copper
  • Electrical Mechanical Controls
  • SystemVu™ Integrated Communicating Controls
  • RTU-Open Communicating Controls
  • Extended Warranty Protection Plans
  • Financing Available
Physical Data

Electric Heat/Electric Cooling & Cooling Only Models (50FC)

Nominal Cooling Ton SizeCooling StagesAHRI Efficiency (SEER) IEERDimensions (in) LxWxHElectrical Heat Nominal kW RangeApprox. Unit Weight (lbs)
31(14.0)74 x 47 x 334.0 to 15.0437
44.0 to 21.0498
56.5 to 24.0511
6215.274 x 47 x 41562
7.588 x 59 x 417.8 to 42.4743
8.588 x 59 x 49805
107.8 to 50.0815
12.5978
1514.7115 x 57 x 6312.0 to 67.01325
17.5127 x 86 x 4918.8 to 75.01800
20141 x 86 x 492000
2514.2141 x 86 x 572174
27.5157 x 86 x 572351

AHRI = Air-Conditioning, Heating & Refrigeration Institute

ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.

IEER = Integrated Energy Efficiency Ratio

SEER = Seasonal Energy Efficiency Ratio

NOTES

1. Rated and certified under ARI Standard 210/240 3-5 ton or 340/360 6+-ton, as appropriate.


2. Ratings are based on:


» Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor air temp and 95°F (35°C) db outdoor air temp.


3. 50FC units generally comply with ASHRAE 90.1-2010 Energy Standard. Please review size specific data for compliance.


4. 50FC units comply with US Energy Policy Act (2005).

QTY