Carrier 38AUQ 1-Stage, Single Circuit Heat Pump 10 Ton, 11 EER, 208/230-3-60

38AUQA12A0A5-0A0A0
$0.00 / EACH
  • : Carrier
  • : Trading Goods (ZAW1)
  • : 03 - Use
  • : Each
  • : Pound(LB)
  • : Standard Item (NORM)
  • Auto Enrichment Status: Ready

with Puron® Refrigerant

6 to 20 Nominal Tons

The Gemini® 38AU series outdoor units and matched with the 40RU series indoor air handlers offer a wide variety of options for your HVAC application needs. This series is designed for long dependable operation whether it's a rooftop or on-the-ground installation. All GEMINI 38AU Condensing Units and 40RU Fan Coils use environmentally sound Puron® refrigerant. Together, they create a reliable split system that provides easy solutions to a wide range of commercial HVAC needs.

Features

Performance Features

  • 38AUQ Heat Pump EERs up to 11.0 and 3.5 COP
  • ASHRAE 90.1 Efficiency Compliant
  • Standard crankcase heater
  • Compressor vibration isolation
  • Low ambient temperature control
  • Unit performance certified in accordance with ARI standard 340/360

Reliability Features

  • High and low-pressure switches
  • Anti-short cycling protection
  • Prepainted, galvanized steel cabinets that passes 500-hour salt-spray test
  • Compressor overload protection
  • Scroll compressor
  • E-Coat coil protection
  • UL, UL, Canada or ETL approved

Installation Features

  • Shipped with Puron (R-410A) refrigerant partial charge
  • Single-piece design
  • Perimeter base rail with forklift slots and lifting holes facilitates rigging
  • Suitable for mounting on the ground or the rooftop
  • 24V control circuit transformer permits quick, easy wiring of thermostats

Maintenance Features

  • Comfort Alert™ diagnostic board
  • Powered and non-powered 115-v convenience outlet
  • Compressor access panel with easy grip handle
  • Easy starting, no-strip screw feature
  • Non-fused disconnect switch

Standard Limited Warranty

  • 5 years parts only on compressor
  • One year parts only on all other parts
Options

Factory-Installed Options

  • Non-fused Disconnect
  • Premium, E-coated condenser coil
  • Convenience outlet (powered)
  • Low ambient temperature Motormaster® control
  • Louvered hail guards

Field-Installed Accessories

  • Low ambient temperature Motormaster® control
  • Louvered hail guard
  • Programmable thermostats
Physical Data

38AUQ/40RUQ AHRI Cooling Ratings

UnitCooling StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)EERIEER
38AUQ07 / 40RUQ071670.06.411.012.6
38AUQ08 / 40RUQ0817.589.08.111.012.0
38AUQ12 / 40RUQ12110112.010.211.012.0
38AUQ16 / 40RUQ16215178.016.810.611.0
38AUQ25 / 40RUQ25220220.020.810.711.0

38AUQ/40RUQ AHRI High Heat Ratings at 47°F (8°C)

UnitHeating StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)COP
38AUQ07 / 40RUQ071666.05.93.30
38AUQ08 / 40RUQ0817.587.07.73.30
38AUQ12 / 40RUQ12110106.09.43.30
38AUQ16 / 40RUQ16215178.015.33.40
38AUQ25 / 40RUQ25220214.017.93.50

38AUQ/40RUQ AHRI Low Heat Ratings at 17°F (-8°C)

UnitHeating StagesNominal Capacity (Tons)Net Cooling Capacity (MBH)Total Power (kW)COP
38AUQ07 / 40RUQ071639.05.22.20
38AUQ08 / 40RUQ0817.552.06.92.20
38AUQ12 / 40RUQ1211070.09.32.20
38AUQ16 / 40RUQ16215108.013.22.40
38AUQ25 / 40RUQ25220130.015.92.40

AHRI = Air-Conditioning, Heating and Refrigeration Institute

ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.

EER = Energy Efficiency Ratio

IEER = Integrated Energy Efficiency Ratio

COP = Coefficient of Performance

NOTES

1. Rated in accordance with ARI Standard 340/360---07, as appropriate.


2. Ratings are based on:


- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.


- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.


3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.

QTY